The CMP Products Falcon Two Bolt single cable cleat is a non-metallic cable cleat which has been designed, constructed, and tested in accordance with the International Standard ‘cable cleats for Electrical Installations’ (IEC 61914:2009). It ensures the retention and securing of single cables, without damaging or deforming the cable. The cable cleat is manufactured from various materials making it suitable for both indoor and outdoor applications. Due to its unique twin arc internal patent pending design profile it exhibits excellent retention, limiting both the axial and lateral movement. The Falcon Two Bolt cable cleats have an excellent range take and are suitable for cable diameters of 38mm up to 135mm in only eight sizes. This cable cleat has two M12 clearance holes for securing it to a mounting surface, which allows for either M10 or M12 fasteners to be used.
Short Circuit Testing to IEC 61914:2009 - Clause 9.5 | ||
Multicore Formation | Parallel Formation | |
Two short circuits (6.4.4) 600mm fixed cleat centres | One short circuit (6.4.3) 600mm fixed cleat centres 105mm cable centres | Two short circuits (6.4.4) 600mm fixed cleat centres 105mm cable centres |
0.1 sec | 0.1 sec | 0.1 sec |
76kA Peak | 110kA Peak | 86kA Peak |
36.2kA RMS | 50.0kA RMS | 40.9kA RMS |
Type 6.1.2. Non Metallic 2BC - Two Bolt Cable Cleat | |
IEC 61914:2009 | |
-40°C to +60°C IEC 61914:2009 clause / part 6.2 |
|
Pass - 120 second flame application time IEC 61914:2009 clause 10.0, 10.1, IEC 60695-11-5 |
|
16kN - 26kN, IEC 61914:2009 clause 9.3 | |
2.75kN - 5kN, IEC 61914:2009 clause 9.4 | |
Pass - Very Heavy IEC 61914:2009 clause 6.3, 6.3.5, 9.2 |
|
Pass - IEC 61914:2009 clause 6.5.1.2, 11.1 | |
Nylon, V0 nylon & LUL approved polymer | |
Black |
**For lateral and axial load ratings or Short circuit ratings of LUL polymer products, please contact CMP.
Нажмите здесь чтобы ознакомиться с технической иллюстрацией
Falcon Part No. | Cable Ø range take (in.) | Dimensions (in.) | Weight W *(LUL +5%) (Oz.) |
||||
W | H | D | P | Fixing Hole Ø | |||
2BC038048 | 1.496 - 1.890 | 3.780 | 2.913 | 2.402 | 65 - 69 | 2 x M10 / M12 | 4.37 |
2BC048058 | 1.890 - 2.283 | 4.213 | 3.307 | 2.402 | 76 - 80 | 2 x M10 / M12 | 5.15 |
2BC058070 | 2.283 - 2.756 | 4.685 | 3.819 | 2.402 | 88 - 92 | 2 x M10 / M12 | 6.21 |
2BC070083 | 2.756 - 3.268 | 5.236 | 4.331 | 2.402 | 102 - 106 | 2 x M10 / M12 | 7.44 |
2BC083097 | 3.268 - 3.819 | 5.787 | 4.882 | 2.402 | 116 - 120 | 2 x M10 / M12 | 8.54 |
2BC096109 | 3.780 - 4.291 | 6.299 | 5.354 | 2.402 | 129 - 133 | 2 x M10 / M12 | 9.74 |
2BC106120 | 4.173 - 4.724 | 6.772 | 5.827 | 2.402 | 141 - 145 | 2 x M10 / M12 | 10.93 |
2BC120135 | 4.724 - 5.315 | 7.362 | 6.417 | 2.402 | 156 - 160 | 2 x M10 / M12 | 12.31 |
Falcon Part No. | Cable Ø range take (mm) | Dimensions mm | Weight W *(LUL +5%) (g) |
||||
W | H | D | P | Fixing Hole Ø | |||
2BC038048 | 38 - 48 | 96.0 | 74.0 | 61.0 | 65 - 69 | 2 x M10 / M12 | 124 |
2BC048058 | 48 - 58 | 107.0 | 84.0 | 61.0 | 76 - 80 | 2 x M10 / M12 | 146 |
2BC058070 | 58 - 70 | 119.0 | 97.0 | 61.0 | 88 - 92 | 2 x M10 / M12 | 176 |
2BC070083 | 70 - 83 | 133.0 | 110.0 | 61.0 | 102 - 106 | 2 x M10 / M12 | 211 |
2BC083097 | 83 - 97 | 147.0 | 124.0 | 61.0 | 116 - 120 | 2 x M10 / M12 | 242 |
2BC096109 | 96 - 109 | 160.0 | 136.0 | 61.0 | 129 - 133 | 2 x M10 / M12 | 276 |
2BC106120 | 106 - 120 | 172.0 | 148.0 | 61.0 | 141 - 145 | 2 x M10 / M12 | 310 |
2BC120135 | 120 - 135 | 187.0 | 163.0 | 61.0 | 156 - 160 | 2 x M10 / M12 | 349 |