E2W CIEL | Industrial Cable Gland For all types of Steel & Aluminium Wire Armoured Lead Sheathed Cables

Industrial Double Seal Cast Integral Earth Lug Cable Gland

• External & Internal Earth Connection
• IThird party short circuit tested
• Metal-to-metal armour clamping
• Direct & remote installation
• Permanently crimped, low impedance earth termination
• Secure against self-loosening
• Displacement type inner seal
• Controlled outer ‘load retention’ seal
• Unique OSTG prevents overtightening
• Deluge protection option
• -60°C to +130°C
• Superior EMC performance

Note: The Symmetrical Fault Current (kA) rating for 1 second applicable to the Cast Integral Earth Lug featured in the E2W CIEL products are as follows:
• 26.0 kA for Cable Gland sizes up to 40
• 43.0 kA for Cable Gland sizes 50S and above.

For under / oversized armour wires click here

Design Specification BS 6121:Part 1:1989, IEC 62444, EN 62444
Mechanical Classifications* Impact = Level 8, Retention = Class D
Enclosure Protection IK10 to IEC 62262 (20 joules) Brass & Stainless Steel only
Electrical Classifications* Category C
GOST R Certificate POCC.GB.HA46.H00140
Marine Approvals LRS: 01/00171 (E1), ABS: 16-LD1472056-PDA
Ingress Protection Rating ** IP66 as standard (IP67, IP68 available upon request)
Cable Gland Material Brass, Electroless Nickel Plated Brass, Aluminium
Seal Material CMP Thermoset Rubber
Cable Type Lead Sheathed & Single Wire Armour (LC/SWA),
Lead Sheathed Aluminium Wire Armour (LC/AWA)
Armour Clamping Detachable Armour Cone & AnyWay Universal Clamping Ring
Sealing Technique CMP Inner Displacement Seal & Unique CMP ‘LRS’ TM Outer Load Retention Seal
Sealing Area(s) Cable Inner Bedding & Outer Cable Sheath
Optional Accessories Locknuts, Earth Tags, Serrated Washers, Entry Thread Seals, Shrouds,Ingress Discs
Optional Installation Tools Spanners

Note : * Mechanical & Electrical Classifications applied as per IEC 62444 & EN 62444
** Refer to Maintaining a Seal for further information on Ingress Protection Ratings

Jump to technical illustration   

Certificates

Click here to view Certificates

Product Selection Table

Click here to view how to order

Cable Gland SizeAvailable Entry Threads "C" (Alternate Metric Thread Lengths Available)Lead Sheath Diameter "A"Overall Cable Diameter "B"Armour RangeAcross Flats "D"Across Corners "D"Protrusion Length "F"Nominal Radius DimensionCIEL Earth Bolt SizeEarth Fault Current Rating (kA)Combined Ordering Reference (*Brass Metric)Cable Gland Weight (Kgs)
Standard
MetricThread Length (Metric) "E"NPTThread Length (Metric) "E"NPTMinMaxMinMaxMinMaxMaxMax"H""G"SizeTypeOrdering Suffix
20SM200.39½'0.78¾'0.240.430.370.630.030.050.941.042.761.131.52M826.020SE2WC1RA0.20
20M200.39½'0.78¾'0.260.530.490.820.030.051.201.322.871.251.65M826.020E2WC1RA0.28
25SM250.39¾'0.801'0.440.760.550.870.050.061.481.633.501.502.00M826.025SE2WC1RA0.44
25M250.39¾'0.801'0.440.760.721.030.050.061.481.633.501.502.00M826.025E2WC1RA0.44
32M320.391'0.981 ¼'0.671.000.931.330.060.081.811.993.391.632.13M826.032E2WC1RA0.51
40M400.591 ¼'1.011 ½'0.871.231.101.590.060.082.172.383.542.002.69M1026.040E2WC1RA0.80
50SM500.591 ½'1.032'1.161.461.391.840.080.102.362.603.582.252.94M1243.050SE2WC1RA0.88
50M500.592'1.062 ½'1.401.681.592.090.080.102.763.043.742.373.13M1243.050E2WC1RA1.04
63SM630.592'1.062 ½'1.581.911.802.340.080.102.953.254.022.763.56M1243.063SE2WC1RA1.64
63M630.592 ½'1.573'1.862.132.152.590.080.103.153.464.092.763.56M1243.063E2WC1RA1.60
75SM750.592 ½'1.573'2.082.372.322.830.080.103.543.904.533.003.88M1243.075SE2WC1RA2.31
75M750.593'1.633 ½'2.332.572.633.090.100.123.944.334.613.254.25M1243.075E2WC1RA2.72
90M900.943'1.694'2.623.043.003.560.120.164.504.955.793.755.00M1243.090E2WC1RA4.42
100M1000.944'1.735'2.993.473.393.990.120.164.845.335.514.025.27M1243.0100E2WC1RA4.82
115M1150.944'1.735'3.393.704.004.340.120.165.255.786.383.755.00M1243.0115E2WC1RA6.19
130M1300.945'1.846'3.824.334.344.850.120.166.006.606.974.025.27M1243.0130E2WC1RA8.54
Dimensions displayed in inches unless otherwise stated
Cable Gland SizeAvailable Entry Threads "C" (Alternate Metric Thread Lengths Available)Lead Sheath Diameter "A"Overall Cable Diameter "B"Armour RangeAcross Flats "D"Across Corners "D"Protrusion Length "F"Nominal Radius DimensionCIEL Earth Bolt SizeEarth Fault Current Rating (kA)Combined Ordering Reference (*Brass Metric)Cable Gland Weight (Kgs)
Standard
MetricThread Length (Metric) "E"NPTThread Length (Metric) "E"NPTMinMaxMinMaxminMaxMaxMax"H""G"SizeTypeOrdering Suffix
20SM2010.0½'19.9¾'6.111.09.515.90.81.2524.026.470.028.638.6M826.020SE2WC1RA0.20
20M2010.0½'19.9¾'6.513.412.520.90.81.2530.533.673.031.841.8M826.020E2WC1RA0.28
25SM2510.0¾'20.21'11.119.314.022.01.251.637.541.389.038.150.8M826.025SE2WC1RA0.44
25M2510.0¾'20.21'11.119.318.226.21.251.637.541.389.038.150.8M826.025E2WC1RA0.44
32M3210.01'25.01 ¼'17.025.523.733.91.62.046.050.686.041.354.0M826.032E2WC1RA0.51
40M4015.01 ¼'25.61 ½'22.031.227.940.41.62.055.060.590.050.868.3M1026.040E2WC1RA0.80
50SM5015.01 ½'26.12'29.537.235.246.72.02.560.066.091.057.274.6M1243.050SE2WC1RA0.88
50M5015.02'26.92 ½'35.642.640.453.02.02.570.177.195.060.379.4M1243.050E2WC1RA1.04
63SM6315.02'26.92 ½'40.148.545.659.42.02.575.082.5102.070.090.5M1243.063SE2WC1RA1.64
63M6315.02 ½'39.93'47.254.254.665.82.02.580.088.0104.070.090.5M1243.063E2WC1RA1.60
75SM7515.02 ½'39.93'52.860.259.072.02.02.590.099.0115.076.298.5M1243.075SE2WC1RA2.31
75M7515.03'41.53 ½'59.165.266.778.42.53.0100.0110.0117.082.6108.0M1243.075E2WC1RA2.72
90M9024.03'42.84'66.677.176.290.33.154.0114.3125.7147.095.3127.1M1243.090E2WC1RA4.42
100M10024.04'44.05'76.088.186.1101.43.154.0123.0135.3140.0102.0133.8M1243.0100E2WC1RA4.82
115M11524.04'44.05'86.094.1101.5110.23.154.0133.4146.7162.095.3127.1M1243.0115E2WC1RA6.19
130M13024.05'46.86'97.0110.1110.2123.23.154.0152.4167.6177.0102.0133.8M1243.0130E2WC1RA8.54
Dimensions displayed in millimeters unless otherwise stated

Technical Illustration

Additional Information

Cable Gland & Enclosure Material Selection ‘Quick Guide’

The specific conditions of any installation will play a major part in the selection of the cable gland material, taking into account the level of environmental exposure along with the nature of the enclosure and cable armour or braid material.

Read more

Visit our Knowledge Base for technical expertise and advice, gathered over CMP's 60+ years' experience in the art of terminating cable glands.

Sign up now